Outputs
Total number of outputs
2
Output signal
switching signal; IO-Link; (configurable)
Electrical design
PNP/NPN
Number of digital outputs
2
Output function
normally open / normally closed; (parameterisable)
Max. voltage drop switching
output DC
[V]
2
Permanent current rating of
switching output DC
[mA]
100
Switching frequency DC [Hz]
< 170
Short-circuit protection
yes
Type of short-circuit
protection
pulsed
Overload protection
yes
Measuring/setting range
Measuring range 0...250 bar 0...3626 psi 0...25 MPa
Set point SP 2.5...250 bar 37...3626 psi 0.25...25 MPa
Reset point rP 1.3...248.8 bar 18...3608 psi 0.13...24.88 MPa
In steps of 0.1 bar 1 psi 0.01 MPa
Factory setting
SP1 = 62.5 bar rP1 = 57.5 bar ou1 = Hno;
SP2 = 187.5 bar rP2 = 182.5 bar ou2 = Hno;
dS1/dS2 = 0 ms dr1/dr2 = 0 ms
coF = 0 % P-n = PnP dAP= 60 ms
Accuracy / deviations
Switch point accuracy
[% of the span]
< ± 0,5 (nach DIN EN 61298-2)
Repeatability [% of the span]
< ± 0,05; (with temperature fluctuations < 10 K)
Characteristics deviation
[% of the span]
< ± 0,5; (linearity incl. hysteresis and repeatability,
limit value setting to DIN EN IEC 62828-1)
Linearity deviation
[% of the span]
< ± 0,1 (BFSL) / < ± 0,2 (LS)
Hysteresis deviation
[% of the span]
< ± 0,2
Long-term stability
[% of the span]
< ± 0,1; (per 6 months)
Temperature coefficient zero
point
[% of the span / 10 K]
< 0,1 (-25...90 °C) / < 0,2 (-40...-25 °C)
Temperature coefficient span
[% of the span / 10 K]
< 0,1 (-25...90 °C) / < 0,2 (-40...-25 °C)
Response times
Response time [ms]
< 3
Software / programming
Parameter setting options
hysteresis / window; normally open / normally closed;
switching logic; switch-on/switch-off delay; Damping